Maximum Rating
60 ekW
Minimum Rating
60 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 3
Voltage
208 to 600 Volts

Financial Programs

  • Downpayment
    >49%
  • Period
    36 months
  • Rate
    0%
%
Period
Leasing agreement amount
Payment type
Annuity
Monthly payment
/ month

Generator Set Specifications

Maximum Rating
60 ekW
Minimum Rating
60 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 3
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1,800 rpm
Duty Cycle
Standby

Engine Specifications

Engine Model
C4.4, In-line 4, 4-cycle diesel
Bore
4.1 in
Stroke
5 in
Displacement
269 in
Compression Ratio
16.7:1
Aspiration
Turbocharged
Fuel System
Electronic (adjustable)
Governor Type
Mechanical, ADEM™A4

Generator Set Dimensions

Length - Maximum
77.2 in
Width - Maximum
43.3 in
Height - Maximum
48 in
Dry Weight - Genset (maximum)
2,054 lb

Standard Equipment:

  • Certificates
    • IBC seismic and wind Certifications
  • Air Inlet System
    • Air cleaner
    • Cartridge type air filter
  • Circuit Breakers
    • Breakers (100% UL rated)
    • 3-Pole 100% rated
    • Second circuit breaker box
    • Power terminal strip
  • Charging System
    • NFPA battery charger UL10A 120VAC
  • Control Panel
    • GCCP 1.2 Control panel
  • Exhaust System
    • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
  • Fuel System
    • Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
  • Control Panels
    • WSS1 Low coolant level shut down
    • FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected
    • NFPA110 bundle includes:
    • WCA1 Low coolant temperature alarm
    • A Coolant heater, remote annunciator or 0.8 power factor test may be required depending on the application
    • PBC10NU NFPA battery charger
    • Oil temperature gauge and sender
    • PAA1 Panel mounted audible alarm
    • Ground fault relay
    • Remote E-stop button
    • Remote annunciator module
    • Audible alarm
    • Volt free contacts genset run and common alarm
    • Discrete I/O module
    • Overload shutdown via breaker
    • Low coolant temperature alarm
    • Protective devices:
    • Fuel level reading
    • Low coolant level shutdown
  • Cooling System
    • Coolant drain line with valve
    • Fan drive, battery charging alternator drive
    • Caterpillar extended life coolant
    • Radiator and cooling fan with guards
    • Radiator stone guard
  • Generator
    • 12 Leads
  • Governing System
    • Mechanical and electrical governing system - model dependent
  • Lube System
    • Oil drain line with valve
    • Lubricating oil
  • General
    • Engine and alternator pre-paint, Caterpillar yellow
  • Starting/charging System
    • Batteries
    • 24V battery with rack and cables

Optional Equipment:

  • Certificates
    • IBC seismic and wind Certifications
  • Alternator System
    • R Frame auxilliary winding
  • Air Inlet System
    • Cartridge type air filter
  • Charging System
    • NFPA battery charger UL10A 120VAC
  • Circuit Breakers
    • Breakers (100% UL rated)
    • 3-Pole 100% rated
    • Second circuit breaker box
    • Power terminal strip
  • Control Panels
    • NFPA110 bundle includes: FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected - WSS1 Low coolant level shut down - WCA1 Low coolant temperature alarm - PAA1 Panel mounted audible alarm - PBC10NU NFPA battery charger - A Coolant heater ,remote annunciator or 0.8 power factor test may be required depending on the application
    • Ground fault relay
    • Remote E-stop button
    • Volt free contacts genset run and common alarm
    • Oil temperature gauge and sender
    • Audible alarm
    • Remote annunciator module
    • Protective devices: Low coolant temperature alarm - Low coolant level shutdown - Fuel level reading - Overload shutdown via breaker
    • Discrete I/O module
  • Cooling System
    • Radiator transition flange
  • Enclosures
    • Sound attenuated enclosure, Level 1
    • External emergency stop
    • Sound attenuated Level 2 Enclosure (White)
    • Panel viewing window
  • Exhaust System
    • 10, 25 and 35 dBA silencer systems
    • Overhead silencer mounting kit
  • Fuel System
    • Emergency vent pipe
    • Tank riser
    • 5 Gallon spill containment
    • 209 and 394 gallon sub-base fuel tanks
    • 5 Gallon fill containment
  • Heating Elements
    • Battery heater
    • Jacket water heater
    • Coolant heater
    • Anti-condensation heater
    • Wiring for canopy space heater
    • Lube oil sump heater
  • Generators
    • Permanent magnet excitation (PMG) generator
    • Cat Alternator
  • Mounting System
    • Seismic vibration isolators
  • Tests
    • 4 Hour factory test
    • Generator test report
    • PGS Test report @ 0.8 power factor
    • PGS Test report @ 1.0 power factor

Specifications

Generator Set Specifications

Maximum Rating
60 ekW
Minimum Rating
60 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 3
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1,800 rpm
Duty Cycle
Standby

Engine Specifications

Engine Model
C4.4, In-line 4, 4-cycle diesel
Bore
4.1 in
Stroke
5 in
Displacement
269 in
Compression Ratio
16.7:1
Aspiration
Turbocharged
Fuel System
Electronic (adjustable)
Governor Type
Mechanical, ADEM™A4

Generator Set Dimensions

Length - Maximum
77.2 in
Width - Maximum
43.3 in
Height - Maximum
48 in
Dry Weight - Genset (maximum)
2,054 lb

Standard/Optional Features

Standard Equipment:

  • Certificates
    • IBC seismic and wind Certifications
  • Air Inlet System
    • Air cleaner
    • Cartridge type air filter
  • Circuit Breakers
    • Breakers (100% UL rated)
    • 3-Pole 100% rated
    • Second circuit breaker box
    • Power terminal strip
  • Charging System
    • NFPA battery charger UL10A 120VAC
  • Control Panel
    • GCCP 1.2 Control panel
  • Exhaust System
    • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
  • Fuel System
    • Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
  • Control Panels
    • WSS1 Low coolant level shut down
    • FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected
    • NFPA110 bundle includes:
    • WCA1 Low coolant temperature alarm
    • A Coolant heater, remote annunciator or 0.8 power factor test may be required depending on the application
    • PBC10NU NFPA battery charger
    • Oil temperature gauge and sender
    • PAA1 Panel mounted audible alarm
    • Ground fault relay
    • Remote E-stop button
    • Remote annunciator module
    • Audible alarm
    • Volt free contacts genset run and common alarm
    • Discrete I/O module
    • Overload shutdown via breaker
    • Low coolant temperature alarm
    • Protective devices:
    • Fuel level reading
    • Low coolant level shutdown
  • Cooling System
    • Coolant drain line with valve
    • Fan drive, battery charging alternator drive
    • Caterpillar extended life coolant
    • Radiator and cooling fan with guards
    • Radiator stone guard
  • Generator
    • 12 Leads
  • Governing System
    • Mechanical and electrical governing system - model dependent
  • Lube System
    • Oil drain line with valve
    • Lubricating oil
  • General
    • Engine and alternator pre-paint, Caterpillar yellow
  • Starting/charging System
    • Batteries
    • 24V battery with rack and cables

Optional Equipment:

  • Certificates
    • IBC seismic and wind Certifications
  • Alternator System
    • R Frame auxilliary winding
  • Air Inlet System
    • Cartridge type air filter
  • Charging System
    • NFPA battery charger UL10A 120VAC
  • Circuit Breakers
    • Breakers (100% UL rated)
    • 3-Pole 100% rated
    • Second circuit breaker box
    • Power terminal strip
  • Control Panels
    • NFPA110 bundle includes: FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected - WSS1 Low coolant level shut down - WCA1 Low coolant temperature alarm - PAA1 Panel mounted audible alarm - PBC10NU NFPA battery charger - A Coolant heater ,remote annunciator or 0.8 power factor test may be required depending on the application
    • Ground fault relay
    • Remote E-stop button
    • Volt free contacts genset run and common alarm
    • Oil temperature gauge and sender
    • Audible alarm
    • Remote annunciator module
    • Protective devices: Low coolant temperature alarm - Low coolant level shutdown - Fuel level reading - Overload shutdown via breaker
    • Discrete I/O module
  • Cooling System
    • Radiator transition flange
  • Enclosures
    • Sound attenuated enclosure, Level 1
    • External emergency stop
    • Sound attenuated Level 2 Enclosure (White)
    • Panel viewing window
  • Exhaust System
    • 10, 25 and 35 dBA silencer systems
    • Overhead silencer mounting kit
  • Fuel System
    • Emergency vent pipe
    • Tank riser
    • 5 Gallon spill containment
    • 209 and 394 gallon sub-base fuel tanks
    • 5 Gallon fill containment
  • Heating Elements
    • Battery heater
    • Jacket water heater
    • Coolant heater
    • Anti-condensation heater
    • Wiring for canopy space heater
    • Lube oil sump heater
  • Generators
    • Permanent magnet excitation (PMG) generator
    • Cat Alternator
  • Mounting System
    • Seismic vibration isolators
  • Tests
    • 4 Hour factory test
    • Generator test report
    • PGS Test report @ 0.8 power factor
    • PGS Test report @ 1.0 power factor