The Emergency Transfer and Load management (XLM) product supports transfer between the utility source and generator bus and allows for sustained parallel operation with the utility for load management applications.
Financial Programs
- Downpayment>49%
- Period36 months
- Rate0%
Technical Summary
- Configuration
- Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
- Modes of Operation
- Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
- Application
- LV and MV ( 208V - 38 kV
Generator Protective Devices
- ANSI Protective Devices
- 15/25, 27/59, 81 O/U, 32, 40, 50, 51
Utility Protective Devices
- ANSI Protective Devices
- 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86
Environmental Parameters
- Certifications
- IBS, CBC, UBC & OSHPD Certified
- Control Panel Enclosure
- NEMA 1 or NEMA 3R, Freestanding Construction
- Operating Temperature
- 0 degrees to 50 degrees C
- Storage Temperature
- -20 degrees C to +60 degrees C
- Low Voltage Standards
- NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1,558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
- Medium Voltage Standards
- NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1,110
Standard Equipment:
- Generator Demand Priority Control
- Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets.
Optional Equipment:
- Data Table Interface
- Accommodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
- Supplemental Hardware Synchronization Check Relay (ansi 25 Device)
- Provides additional discrete synchronization protection
- Remote Power Monitoring System
- To monitor breaker status, alarms, metering and other operating parameters
Specifications
Technical Summary
- Configuration
- Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
- Modes of Operation
- Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
- Application
- LV and MV ( 208V - 38 kV
Generator Protective Devices
- ANSI Protective Devices
- 15/25, 27/59, 81 O/U, 32, 40, 50, 51
Utility Protective Devices
- ANSI Protective Devices
- 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86
Environmental Parameters
- Certifications
- IBS, CBC, UBC & OSHPD Certified
- Control Panel Enclosure
- NEMA 1 or NEMA 3R, Freestanding Construction
- Operating Temperature
- 0 degrees to 50 degrees C
- Storage Temperature
- -20 degrees C to +60 degrees C
- Low Voltage Standards
- NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1,558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
- Medium Voltage Standards
- NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1,110
Standard/Optional Features
Standard Equipment:
- Generator Demand Priority Control
- Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets.
Optional Equipment:
- Data Table Interface
- Accommodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
- Supplemental Hardware Synchronization Check Relay (ansi 25 Device)
- Provides additional discrete synchronization protection
- Remote Power Monitoring System
- To monitor breaker status, alarms, metering and other operating parameters